Accuracy:
2 % or ±10 ppb TFC, whichever is greater at pH <7.5
Accuracy 2:
2 % or ±10 ppb HOCl, whichever is greater at pH <8
Calibration Interval:
2 months
Calibration Method:
Zero Calibration: electrically (automatic) or with de-chlorinated water
Calibration: Comparison of lab method with
process sample
pH Calibration: Single- or two-point using standards
or comparison of lab method with
process sample
Description :
9184sc Hypochlorous Acid Chlorine Amperometric Sensor
Enclosure Rating:
IP66 / NEMA 4X
Flow:
0.25 L/h (200 - 250 mL/min) auto--regulated by flow through cell
Interferences:
No interference from chloramines.
Chlorine dioxide and ozone interfere with
measurement.
Lower Limit of Detection (LOD):
0.005 mg/L HOCl
Maintenance Interval:
6 months Measurement Cell: for membrane and electrolyte, typical
Maintenance Interval 2:
1 1.5 pH Cell: typical
Measuring Interval:
Continuous
Measuring Principle:
Amperometric/Membrane (electrode,
membrane, electrolyte)
Mounting:
Flat, vertical surface (panel, stand, etc.)
Operating temperature range:
0 - 45 °C
Parameter:
Hypochlorous Acid Only Chlorine
pH Range:
4 - 8, acidification unit available for pH > 8
Pressure Range:
0.1 - 2 bar in flow cell
Range:
0 - 20 mg/L hypochlorous acid HOCl
Relative Humidity:
0 - 90 % non-condensing
Response time:
90 % in less than 90 seconds
Sample Input:
0.25 " outer diameter
Sample Output:
0.5 " inner diameter
Sample Temperature:
2 - 45 °C
Standard deviation:
0.7 %
Storage conditions:
-20 - 60 °C
Temperature Compensation:
Automatic over sample temperature range
Automatic over sample temperature range
Warranty:
12 months
Weight:
6.5 kg
What's included?: