Alarm:
Low alarm point, low alarm point deadband, high alarm point, high alarm point deadband, off delay, and on delay
Analog Inputs:
No Input Module
Analog Output:
One 4-20 mA Output Module
Analog Output Functional Mode:
PID, high/low phasing, setpoint, deadband, overfeed timer, off delay, on delay
Analog Outputs:
Up to 12 analog/digital inputs scalable via digital network
Certifications:
European Certifications:
CE per 73/23/EEC and 89/336/EEC
TUV-GS to EN 61010-1
EN 61326 Amd's 1 & 2
Communication:
Modbus® (RS485): Advanced communications/networking with PLC or SCADA system directly from analyzer
Profibus® DP/V1 (certified)
GSM/GPRS Quad-band cellular module (FCC and IC approved, EU and US only)
Ethernet service port, RJ45, 10 MB/s
Communication Capabilities:
None
Conduit for Relay Connection:
No
Dimensions (H x W x D):
242 mm x 315 mm x 120 mm
Display:
¼ inch VGA graphical backlit TFT color Glas/Glas-Touch screen, high resistance 320 x 240 pixels
Display Resolution:
320 x 240 Pixel, 256 colours glass/glass-touch supplied by display module
Display Viewing Area:
11.4 x 8.6 cm (4.5 x 3.4 in)
Electrical Certifications:
CE 2006/95/EC, EMV 2004/108/EC, TUV-GS EN61010-1, DIN EN 61326
Enclosure Rating:
IP65
Inputs:
Up to 12 analogue 0-20 mA, maximum impedance 500 Ohms per probe module. Additional inputs are available with additional probe modules.
Material Enclosures:
ABS (display module) and metal (probe module) enclosure with corrosion resistant finish
Mounting:
Surface, panel, and pipe (horizontal and vertical) with optional sun shield
Mounting Configurations:
Surface, panel, and pipe (horizontal and vertical) with optional sun shield
Operating temperature range:
-20 - 55 °C / 0 - 95% relative humidity, non-condensing
Output:
Up to 12 analogue 0/4-20 mA, maximum impedance 500 Ohms per probe module.
Additional analogue outputs with additional probe modules. Optional digital communcations via Modbus (RS485) and Profibus DP/V1.
Outputs:
Up to 12 analog 0/4-20 mA, maximum impedance 500 Ohms per probe module.
Additional analog outputs with additional probe modules. Optional digital communcations via Modbus® (RS485) and Profibus® DP/V1.
Power Options:
100-240V AC, EU Power Cord
Prognosys:
No
Relays:
4 Relays
RTC Module:
No
Sensors:
2 Sensors
Storage conditions:
-20 to 70 °C (-4 to 158 °F), 0 to 95% relative humidity, non-condensing
Warranty:
12 months
Weight:
Approximately 6.5 kg (depending on configuration)
What's included?: